SCO Privately Funded Design Exemption 2011 (PDF)
| COMPONENTS | BASE | POSSIBLE UPGRADE | NOTES |
|---|---|---|---|
| Structural Framing Systems | Any strutural framing meeting the NC Building Codes | Steel with metal studs | Careful consideration should be observed about the use of Masonry shafts due to incompability |
| Exterior Cladding | Brick veneer with cast stone trim | NA | |
| Exterior Cladding | Reduce Curtainwall to storefront/steel frame. | Main entrance only | |
| Roofing System Slope | 30 Year ashpalt shingle | Metal/Slate | |
| Roofing System Low Slope | 20 Year Single Ply | 30 Year Buildt-Up Roof | |
| Interior Wall Systems | Regular 5/8” drywall | Impact Resistance Drywall | |
| Doors and Frames | Closet doors only six panel residential. All others solid core | Solid core wood doors at entrances and bedrooms Closet & bathroom doors solid core / six panel residential | |
| Windows | Vinyl | Aluminum | |
| Cabinetry | Residential Grade | Finish | |
| Fireproofing | To be per NCBC, no exceptions | ||
| Fire Sprinkler System | NFPA 13R (up to 4 story building) | NFPA 13 Light Hazard | Must use NFPA 13 in all common use areas |
| Waste Piping | PVC pipe | Cast Iron | Must use cast iron on all waste verticals & under building elbows/horizontals |
| Site Waste Piping | PVC pipe | NA | Must use cast iron or steel sleeves under vehicle traffic area |
| Water Distribution | CPVC or PEX | Copper | PVC not allowed |
| Toilet Type | Tank Type | Power assisted flush | |
| Hot Water Distribution | Individual Electric water heaters | NA | Must meet the 30% energy mandate for whole building |
| Mechanical Systems | PTAC | Four Pipe Fan Coil | |
| Telecom & Low-voltage wiring | Plenum rated wiring | Where plenum ceiling exists only, supported in accordance w/ NEC | |
| Electrical Wiring | MC Cable, 1/2", up to #12 AWG Solid copper w/ ground | EMT | Must use EMT in all common use areas |
| Fire Alarm | Plenum rated wiring | Red MC Cable | Can use as specified in University Guidelines |
| Service Feeders | Aluminum Feeders > #1 AWG | Copper | |
| Main Distribution Panel | Load-center Panels | Copper Bus, Bolt-on Breakers | |
| Transformers | Aluminum Feeders | Copper | |
| Note: Apply only to privately funded projects such as Foundation projects and single family dwelling such as Chancellors' residences and Park Rangers residences. |